California Code of Regulations, Title 8, Section 536. Piping Standards. (2024)

Skip to Main Content

This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.

Subchapter 1. Unfired Pressure Vessel Safety Orders
Article 7. Compressed and Liquefied Natural Gas System

Return to index
New query

(a) General.

(1) All pipe, tubing, fittings and other piping components between the tank and the first shutoff valve shall be designed for the full range of pressures, temperatures and loadings to which they may be subjected with a factor of safety of at least 8 based on the minimum specified tensile strength at room temperature. All other pipe, tubing, fittings and other piping components shall be suitable for the full range of pressures, temperatures and loadings to which they may be subjected with a factor of safety of at least 4. In no case may underground piping be less than Schedule 80 for piping systems having a working pressure exceeding 100 psi. Any material used, including gaskets and packing, shall be compatible with natural gas and its service conditions.

(2) All piping and tubing shall be run as directly as practical with adequate provisions for expansion, contraction, jarring, vibration and settling. Exterior piping may be either buried or installed aboveground and shall be well supported and protected against mechanical damage.

Underground piping shall be buried not less than 18 inches below the surface of the ground unless otherwise protected. All underground piping shall be protected from corrosion by coating in compliance with Section 533(b) or equivalent. Zinc coatings (galvanizing shall not be considered adequate protection for piping below ground.

(3) All welded piping shall be fabricated and tested in accordance with the ANSI Code for Pressure Piping, Petroleum Refinery Piping, B31.3, 1966 Edition or equivalent.

(4) All valves shall be suitable for the full range of pressure and temperature to which they may be subjected. The manufacturer shall stamp or otherwise permanently mark the valve body to indicate the service ratings. Other piping components such as strainers, snubbers and expansion joints shall also be permanently marked by the manufacturer to indicate the service ratings. All materials such as valve seats, packing, gaskets, diaphragms, etc. shall be resistant to the action of natural gas under the conditions to which they are subjected.

(5) Use of the following is prohibited:

(A) Valves, co*cks, fittings and other piping components of cast iron or semisteel other than ASTM Specifications A-536-67, Grade 60-40-18; A-395-68; A-47-68, Grade 35018 and A-445-66 unless they have pressure-temperature ratings at least equal to 1 1/2 times the design service conditions. In no case shall valves of cast iron or semisteel other than the 3 ASTM specifications listed above be used for primary stop valves.

(B) Street ells and screwed service tees.

(C) Valves of a design that will allow the valve stem to be removed without removal of complete valve bonnet or disassembly of the valve body.

(D) Plastic pipe, tubing, hose and fittings, without written permission from the Division.

(E) Valves with valve stem packing glands which cannot be repacked under pressure, unless there is another stop valve of acceptable type between them and the vessel. This does not apply to service valves.

(F) Aluminum tubing for exterior locations and threaded aluminum connections and adapters that are required to be connected or disconnected as part of the filling or transferring operation for those connections and adapters that are specifically designed with special threads suitable for this service.

(G) Pipe nipples in lieu of couplings or flanges in tank connections.

(H) Copper alloy with copper content exceeding 70 percent.

(b) Compressed Natural Gas. Hose shall not be used in lieu of manifolds, piping or tubing between dispensing tanks and cylinders and the connection for the loading and/or unloading hose connections, except that a section of metallic hose not to exceed 24 inches in length may be used in each pipeline to provide flexibility where necessary. Each section shall be so installed that it will be protected against mechanical damage and be readily visible for inspection. The manufacturer's identification shall be retained in each section.

(c) Liquefied Natural Gas.

(1) Flanged joints or threaded joints which have not been seal welded on liquid lines between the tank and the first shutoff valve are prohibited.

(2) All LNG piping over 2-inch pipe size shall be welded flanged or silver brazed with a material having a melting point exceeding 1,000 degrees Fahrenheit. Compression type couplings and threaded joints shall not be used except that seal welded threaded joints may be used.

(3) Piping 2-inch or smaller may be threaded, welded or flanged except as prohibited in 536(c)(1).

(4) Threaded nipples and pipe shall be at least Schedule 80.

(5) Plugs shall be solid or else they shall be bull plugs of at least Schedule 80 seamless pipe.

(6) For service temperatures of minus 20 degrees Fahrenheit or above, threaded piping and tubing with compression type couplings may be used except as prohibited in 536(c)(2).

(7) Pipe supports for piping having a service temperature below minus 20 degrees Fahrenheit shall be designed to minimize heat transfer so that support steel embrittlement

and piping restraints caused by ice formation will be prevented.

(8) Bellows type expansion joints in low temperature service shall be provided with external insulation that will prevent ice from forming on the bellows.

HISTORY:

1. Amendment of subsections (a)(1) and (a)(5)(F) filed 3-29-74; effective thirtieth day thereafter (Register 74, No. 13).

Go Back to Article 7 Table of Contents

California Code of Regulations, Title 8, Section 536.  Piping Standards. (2024)

FAQs

California Code of Regulations, Title 8, Section 536. Piping Standards.? ›

The California Code of Regulations, Title 8, Section 536, outlines specific requirements for piping and tubing, emphasizing the need for careful consideration of factors like expansion, contraction, and vibration. These regulations ensure that all mechanical piping systems are safe, reliable, and efficient.

Can I use galvanized pipe for natural gas in California? ›

❖ Steel pipe must be Schedule 40 or heavier, must comply with one of the listed standards and can be black iron or galvanized. Contrary to popular belief, natural gas does not adversely react with the zinc coating on galvanized pipe.

What is the code for underground gas line in California? ›

Section 1216 - Installation (a) All main line gas piping installed below ground shall have a minimum earth cover of: (1) twenty-four (24) inches or, (2) eighteen (18) inches when installed in the same trench as other utilities; and covered with clean fill free from stones, boulders, cinderfill, construction debris or ...

What kind of pipe is used for natural gas in homes? ›

What type of steel pipe is used for gas lines? The most common gas piping is black steel. Galvanized steel, copper, brass or CSST (Corrugated Stainless Steel Tubing) also can be used in some areas, but some utilities specifically prohibit the use of copper.

How deep do water lines need to be in California? ›

For example, underground pipes are placed at least 12 inches (30.48 cm) below the slab in California, while plumbing in Alaska is done at least 100 inches (254 cm) deep. If pipes are placed too close to the surface, you may not get cold water during summer, and during winter, your water may not heat up fast enough.

Is galvanized pipe ok for gas lines? ›

Many areas do not allow galvanized pipe underground for gas piping and factory coated steel pipe must be used. In some areas plastic pipe is allowed underground (with electric wire above it to allow for locating of that plastic gas pipe as well as warning tape above that pipe as well).

Can you use copper for gas line in California? ›

The proposed building standards state that gas piping may be wrought iron, steel, yellow brass, or types K, L or ACR copper tube. Approved polyethylene pipe may be used in underground applications.

What gas pipe can be run underground? ›

Polyethylene gas piping systems are specifically engineered and certified for the underground environment.

Can galvanized pipe be buried? ›

Consequently, galvanized steel is preferred for structures that are partially exposed to the atmosphere and partially buried, since steel performs unpredictably in-ground while zinc provides the durability above-ground.

What is the code for gas pipeline? ›

IS 15729:2007 This code covers the commissioning, operation andmaintenance and safety aspects of natural gas pressureregulating and metering terminal. INDIAN STANDARDS FOR NATURAL GAS PIPELINE SYSTEM1.

Can I use black pipe for natural gas underground? ›

This is especially important if you're supplying gas or water to rural areas. The natural heat resistance of these pipes can help, but underground environments tend to be moist or easily reached by water. It is not recommended to bury black iron pipes unless you cover them in protective coating against oxidation.

Is PVC pipe OK for natural gas? ›

The most common materials used to make gas piping are steel, black iron, polyvinyl chloride (PVC), high-density polyethylene (HDPE) and copper. Some utilities prohibit some of these materials, so be sure to check with your local utility to determine what is allowed in your area before you install any.

Can PEX be used for natural gas? ›

Can PEX be used for gas line? The common piping used for gas lines is black steel, but PEX has become a popular choice for running natural gas and propane gas lines underground. It is yellow polyethylene similar to plumbing PEX, but the walls aren't as thick.

Is PVC pipe legal in California? ›

The California Building Standards Commission (BSC) has approved a final Environmental Impact Report (EIR) prepared by the state's Housing and Community Development (HCD) Department, with the result that chlorinated polyvinyl chloride (C-PVC) may now be used for hot and cold potable water distribution in houses, ...

Is 2 feet deep enough for water line? ›

Code Requirements for Water Lines

Both the IPC and IRC state that all water lines as well as sewer lines must be a minimum of 12 inches below grade, i.e., a foot underneath ground level.

Can a water pipe be above ground? ›

Piping systems installed above ground must be designed to allow compensation for movement caused by thermal expansion and contraction. This applies to outdoor applications primarily, but also applies to buildings that are not heated or cooled.

What pipelines go to California gas? ›

Delivery of Supplies

The major interstate pipelines that deliver out-of-state natural gas to California gas utilities are Gas Transmission Northwest Pipeline, Kern River Pipeline, Transwestern Pipeline, El Paso Pipeline, Ruby Pipeline, Mojave Pipeline, and Tuscarora.

Are galvanized pipes legal? ›

While galvanized pipe is allowed in most building codes, it has corrosion issues when used for hot, softened water service. The low mineral content in soft water is desirable for reducing scale build-up, but detrimental to corrosion resistance.

What schedule pipe is used for natural gas? ›

All pipe used for the installation, extension, alteration, or repair of any gas piping shall be standard weight Schedule 40 wrought iron or steel (galvanized or black) or corrugated stainless steel tubing.

Can natural gas be ran through copper pipe? ›

Copper tubing can be used to supply both low pressure natural gas systems (those operating at less than 0.5 pounds-per-square-inch-gauge) and elevated pressure systems up to 5 psig. Currently, 2 psig systems are the most common elevated pressure systems used for residential installations.

Top Articles
Latest Posts
Article information

Author: Ms. Lucile Johns

Last Updated:

Views: 6201

Rating: 4 / 5 (41 voted)

Reviews: 88% of readers found this page helpful

Author information

Name: Ms. Lucile Johns

Birthday: 1999-11-16

Address: Suite 237 56046 Walsh Coves, West Enid, VT 46557

Phone: +59115435987187

Job: Education Supervisor

Hobby: Genealogy, Stone skipping, Skydiving, Nordic skating, Couponing, Coloring, Gardening

Introduction: My name is Ms. Lucile Johns, I am a successful, friendly, friendly, homely, adventurous, handsome, delightful person who loves writing and wants to share my knowledge and understanding with you.